Ambient temperature of UPS lead-acid battery

by:Power Kingdom     2021-07-01
Labels: 1. The storage environment temperature of UPS lead-acid batteries is best to be stored in a dry, clean and ventilated environment of 10-20. 2. The use temperature of UPS lead-acid batteries is -20-----+50, but When the ambient temperature is 10-30, a longer life can be obtained. 3. The voltage of the UPS lead-acid battery refers to the charging voltage value at an ambient temperature of 25. When the temperature difference exceeds 10, the floating charging voltage must be corrected, otherwise the battery will be damaged. When the ambient temperature rises by 1, the float charging voltage should be lowered to 0.003V/single cell; on the contrary, the float charging voltage should be increased by 0.003V/single cell.