Question: What happens if the UPS battery does not float according to the regulations?
by:Power Kingdom
2021-07-01
Label: What happens if the UPS battery does not float in accordance with the regulations? Answer: It is more appropriate to set the float charging voltage to 2.23V/cell (25°C). If you do not work in this floating charge range, but use 2.35V/cell (25℃), thermal runaway will occur after 4 months of continuous charging; or use 2.30V/cell (25℃) and charge continuously for 6~ Thermal runaway will occur in 8 months; if 2.28V/cell (25°C) is used, severe capacity drops will occur for 12 to 18 consecutive months, leading to thermal runaway.